Message requests must be transmitted from the host to the CompuScale III in the following format.
som DEVICE MT eom
Example:
Data ASCII Example
Field Character Description
som STX start of message
DEVICE 01 for CompuScale III # 1
MT 50 material flow rate request
eom CR end of message
MESSAGE RESPONSES
The CompuScale III response to a flow rate (MT=50) load (MT=51) or speed (MT=52) message request will
be in the following format.
som DEVICE MT READING eom
Example:
Data ASCII Example
Field Character Description
som STX start of message
DEVICE 00 from CompuScale III # 0
MT 50 material flow rate response
READING 392.5 is 392.5
eom CR end of message
The response to a material total (MT=53) message request will be in the following format.
som DEVICE MT READING UNITS eom
Example:
Data ASCII Example
Field Character Description
som STX start of message
DEVICE 00 from CompuScale III # 0
MT 53 material total response
READING 129.2 is 129.2
UNITS MT Metric Tonnes
eom CR end of message
PL-367 10 – 4