24 = energize on low Aux. volts
25 = de-energize on high Aux. volts
26 = energize on high Aux. volts
27 = de-energize up control on head
28 = energize up control on head
29 = de-energize down control on head
30 = energize down control on head
31 = de-energize up control on analog
32 = energize up control on analog
33 = de-energize down control on analog
34 = energize down control on analog
35 = ( pulse ) flow totalizer
36 = ( pulse ) sampler by volume
37 = ( pulse ) sampler by time
38 = ( pulse ) by time of day
P16 / P19 / P22 relay 1 / 2 / 3 high setpoint
P17 / P20 / P23 relay 1 / 2 / 3 low setpoint
P24 mA assignment
0 = flow rate
1 = head
2 = velocity
3 = temperature
P25 If custom mA, 20 mA = ?
0 = normal
0 = custom
P26 mA span
0 = 4-20 mA
1 = 0-20 mA
7ML19985AB01 OCM III 46