START UP
HARDWARE SET UP
HOST / MILLBUS BAUD RATE
Determine the serial communication baud rate of the host computer or
PLC and open the SW 1 contact (1-5) corresponding to the desired
baud rate. (Refer to Functional/Product Load Factor.)
Close all other baud rate contacts.
HOST / MILLBUS WORD LENGTH
Determine the word length of each character of the host serial
communication and set SW1 contact 6 accordingly. 7 bit word, even
parity, one stop bit or 8 bit word no parity, one stop bit.
SELF TEST
Close contact 8 for normal operation.
BIC-II I. D. #
Each BIC-II connected to the host computer or PLC must be assigned an identification number from 1 - 31.
Set contacts to correspond to the desired identification number as follows :
96/01/09
BIC-II SW 2 Contact BIC-II SW 2 Contact
I. D. #12345I. D. #12345
01 occcc
02 coccc 17 occco
03 ooccc 18 cocco
04 ccocc 19 oocco
05 ococc 20 ccoco
06 coocc 21 ococo
07 o o o c c 22 c o o c o
08 c c c o c 23 o o o c o
09 occoc 24 cccoo
10 c o c o c 25 o c c o o
11 o o c o c 26 c o c o o
12 ccooc 27 oocoo
13 ocooc 28 ccooo
14 coooc 29 ocooo
15 ooooc 30 coooo
16 cccco 31 ooooo
c = closed o = open
BIC-II I.D.
(e.g. #1)
16 /
8/
4/
2/
1/
board A
SW 2
12345
OPEN
PL-371 4 – 1